MODBUS-to-HART module for 2-wire, 3-wire, or 4-wire transmitters. Customization available.

Product Details

  • Complies with FCG certification test standards for the HART protocol.

  • TTL 3.3V Level MODBUS Interface

  • 25mmx25mm Ultra-compact design

  • Provide Windows configuration software and DD image file.

  • Supports up to 6 device variables

  • Support dynamic variable mapping configuration

  • Built-in unit auto-converter

  • Supports register calibration features (e.g., setting flow coefficients for flow meters).

  • YHM-1112-2(2-wire version)Can output 3.3V/12mA power from the base plate (supplied by 24V/300Ω, with loop current of 3.7mA)

  • YHM-1112-2(2-wire version)HART bus interface includes built-in reverse-polarity protection diode and TVS protection

  • YHM-1112-3(3-wire version)Current output port with built-in reverse current protection and TVS protection

  • Four-layer PCB design with high precision and strong interference resistance

    Technical Specifications

No.

Content

Metric

1

Bus Power (YHM-1112-2)

10–33V

2

Bus Interface (YHM-1112-2)

2-wire 4-2 0mA + HART, with reverse polarity and TVS protection

3

Output Power (YHM-1112-2)

3.3V / 12mA, Ripple VRMS≤1 mV

(Powered by 24V/300Ω, loop current 3.7mA)

4

Power Supply (YHM-1112-3)

8-33V

5

Bus Interface (YHM-1112-3)

3-wire 4-20mA+HART

Current output with anti-backflow and TVS protection

6

Modbus Interface

TTL (supports MODBUS RTU master communication protocol)

7

Isolate

No isolation between bus and Modbus interface

8

Operating Temperature

-40 ~ 85 ℃

9

Operating Humidity

(5~95)%RH

10

Storage Temperature

-55 ~ 105℃

11

Start Time

≤1 seconds

12

Last updated

0.2 seconds

13

Damping Adjustment

Time constant 0~32 seconds

14

Alarm Signal

High/Low alarm current 21.75mA/3.7mA;

Upper/Lower current limit 20.8mA/3.8mA

15

Current accuracy

0.05%FS( (room temperature)

16

Current temperature drift

30 ppm

17

Intrinsic Safety Rating

Supports Ex ia IIC T4/T6 Ga

18

Electromagnetic Compatibility

The device can be designed to meet the following requirements when combined with a base plate:

Complies with the immunity requirements for industrial environments specified in GB/T 18268.1-2010, "Electromagnetic compatibility of electrical equipment for measurement, control and laboratory use — Part 1: General requirements."